(13) Where NEC jurisdiction applies; as 5,000-volt nonshielded power cable, Type MV-90, for use at conductor temperatures not exceeding 90°C in wet or dry locations. Cables meet requirements of Article 310.6 of the National Electrical Code.
(14) Where NEC jurisdiction applies; as 5,000- volt non-shielded power cable, Type MV-90, for use at conductor temperatures not exceeding 90°C in wet or dry locations. Cables meet requirements of Article 310-6 of the NEC.
(13) Medium voltage MV-105 power cable for use in main feeder, distribution and branch circuits in industrial, commercial and electric utility installations. Cables may be used in wet or dry locations in circuits not exceeding 5000 volts 133% insulation level or 8000 volts 100% insulation level, at conductor temperatures not exceeding 105°C for normal, 140°C for emergency overload and 250°C for short-circuit conditions. Suitable for installation in conduit, tray, trough, ducts, aerial and direct burial applications.
(11) As medium voltage MV-90 power cable for use in main feeder, distribution and branch circuits in industrial, commercial and electric utility installation. Cables may be used in wet or dry locations in circuits not exceeding 15000 volts 100% insulation level, at conductor temperatures not exceeding 90°C for normal, 130°C for emergency overload and 250°C for short circuit conditions. Suitable for installation in conduit, tray, trough, ducts, aerial and direct burial applications.
(11) As medium voltage MV-105 power cable for use in main feeder, distribution and branch circuits in industrial, commercial and electric utility installations. Cables may be used in wet or dry locations in circuits not exceeding 15000 volts 133% insulation level, at conductor temperatures not exceeding 105°C for normal, 140°C for emergency overload and 250°C for short-circuit conditions. Suitable for installation in conduit, tray, trough, ducts, aerial and direct burial applications.
(18) Cable is suitable for use in dry or wet locations at conductor temperatures not exceeding 90°C normal use, 130°C emergency overload, 250°C short circuit. All sizes may be installed in conduit, duct, or directly buried.
Commercial, industrial and utility projects such as pulp and paper mills, petrochemical plants, steel mills, textile mills, water and sewage treatment facilities, environmental protection systems, railroads, mines and both fossil fuel and nuclear powered generating stations.
(39) Class B strand, bare annealed copper, insulated with heat and moisture resistant XHHW . The conductors shall be cabled in a left hand lay and a messenger of 30% E.H.S. copperclad steel shall be laid parallel and banded with a rounded edge flat bare copper binding strap.
(14) Where NEC jurisdiction applies; as 5,000 volt non-shielded power cable, Type MV-90 Dry, for use at conductor temperatures not exceeding 90°C in dry locations. Cables meet requirements of Article 310-6 of the NEC.
(14) 5000 volt shielded power cable, Type MV-90, for general purpose applications in accordance with the NEC at conductor temperatures not exceeding 90°C in wet or dry locations for normal operation, 130°C for emergency overload, and 250°C for short circuit conditions. Suitable for installation in conduit, trough, ducts, aerial and direct burial applications.
(11) As medium voltage MV-90 power cable for use in main feeder, distribution and branch circuits in industrial, commercial and electric utility installations. Cables may be used in wet or dry locations in circuits not exceeding 15000 volts, 100% insulation level, at conductor temperatures not exceeding 90°C for normal, 130°C for emergency overload and 250°C for short-circuit conditions. Suitable for installation in conduit, trough, ducts, aerial and direct burial applications.
(11) As medium voltage MV-90 power cable for use in main feeder, distribution and branch circuits in industrial, commercial and electric utility installations. Cables may be used in wet or dry locations in circuits not exceeding 15000 volts, 100% insulation level, at conductor temperatures not exceeding 90°C for normal, 130°C for emergency overload and 250°C for short-circuit conditions. Suitable for installation in conduit, trough, ducts, aerial and direct burial applications.
(18) Phase identified, (Color coded tape (Black, Red, Blue) applied under the metallic shielding tape) and cabled together with fillers and bare copper ground conductor.